Bleed, Inhibitor, Dual Biocides (7-day timers)
|
|
Controls Tower TDS via bleed. Includes inhibitor and dual biocide dosing via 7-day timer programs
|
|
 |
|
DIGICHEM-AB2-V
| |
Tower Bleed & Dosing System with peristaltic pumps
|
|
|
|

| |
Features
- Supersedes DIGICHEM-AB2
- On-board data logging
- NEW Black EPDM based squeeze tube with better chemical compatibility & longer tube life
- Digital controller, pumps & manifold mounted on PVC back panel
- Bleed Control - via solenoid valve
- Inhibitor Dosing - reduces corrosion
- Dual Biocide Dosing for system disinfection (via 10 x 28-day timer programs)
- Pre-bleed & Bleed Lock-out
- Self priming peristaltic pumps (1.3l/hr,3bar)
- Condenser pump override facility during biocide dosing with delay-off timer
- Fail-safe alarm relay with remote power failure detection
- Options & variations available - download data sheet
|
| |
Data Sheet
Instruction Manual
Installation Drawings
More Info
|
Glossary |
Search |
Top
|
 |
|
DIGICHEM-AB2-V-CABG
| |
DIGICHEM-AB2-V in IP66 hinged lockable cabinet
|
|
|
|

| |
Features
- Similar features to DIGICHEM-AB2-V
- Digital controller & pumps in hinged lockable, PC+ABS cabinet, mounted with manifold on separate PVC back panel
- Weatherproof - IP66 rated
|
| |
Data Sheet
Instruction Manual
Installation Drawings
More Info
|
Glossary |
Search |
Top
|
 |
|
DIGICHEM-AB2-VB-CABG
| |
DIGICHEM-AB2-V-CABG with Actuated Ball valve for Bleed
|
|
|
|

| |
Features
- Similar features to DIGICHEM-AB2-V
- Belimo actuated ball valve for bleed for improved reliability
- Digital controller, pumps & manifold in hinged lockable, PC+ABS cabinet
- Weatherproof - IP66 rated
|
| |
Data Sheet
Instruction Manual
Installation Drawings
More Info
|
Glossary |
Search |
Top
|
 |
|
DIGICHEM-X/3S-EMEC3-V
| |
Tower Bleed & Dosing System with EMEC solenoid pumps - Degassing Head available on One Biocide Pump as an option
|
|
|
|

| |
Features
- Supersedes DIGICHEM-X/3S-EMEC3
- On-board data logging
- Digital controller, pumps & manifold mounted on PVC back panel
- Bleed Control - via solenoid valve
- Inhibitor Dosing - reduces corrosion
- Dual Biocide Dosing for system disinfection (via 10 x 28-day timer programs)
- Pre-bleed & Bleed Lock-out
- EMEC solenoid pumps, 2.2l/hr, 10bar
- Condenser pump override facility during biocide dosing with delay-off timer
- Fail-safe alarm relay with remote power failure detection
- Options & variations available - download data sheet
|
| |
Data Sheet
Instruction Manual
More Info
|
Glossary |
Search |
Top
|
 |
|
DIGICHEM-X-3S-EMEC3-V-CABG
| |
DIGICHEM-X/3S-EMEC3-V in IP66 hinged lockable cabinet - Degassing Head available on One Biocide Pump as an option
|
|
|
|

| |
Features
- Similar features to DIGICHEM-X/3S-EMEC3-V
- Digital controller & pumps in hinged lockable, PC+ABS cabinet, mounted with manifold on separate PVC back panel
- Weatherproof - IP66 rated
|
| |
Data Sheet
Instruction Manual
More Info
|
Glossary |
Search |
Top
|